100 Challenging Problems Solved | Series 001 How Can Hospitals Address “Disinfection Gaps” Caused by Sodium Thiosulfate in Wastewater?

14 - Sep - 2026

Chlorine dioxide is widely used in hospital wastewater disinfection. However, one easily overlooked issue can affect disinfection performance: some laboratory wastewater or wastewater from specific hospital processes may contain sodium thiosulfate and other reducing substances. When these substances enter the main treatment system, they may increase chlorine dioxide demand and interfere with residual disinfectant control.

“Disinfection Gaps”: An Easily Overlooked System Risk

When wastewater containing sodium thiosulfate or other reducing substances enters the treatment system, it may react relatively quickly with chlorine dioxide through oxidation-reduction reactions.

Sodium thiosulfate is a strong reducing agent. It can rapidly consume chlorine dioxide, causing the effective chlorine dioxide residual to decrease and producing corresponding reduction products.

When wastewater is poorly mixed, reducing substances are locally concentrated, or short-term loading fluctuations are significant, local oxidant demand may suddenly increase. This can cause the chlorine dioxide residual in certain areas to drop substantially. In this article, this phenomenon is figuratively referred to as a “disinfection gap.”

If the local chlorine dioxide residual and effective contact conditions are insufficient, microbial inactivation may be reduced, increasing the risk that microbiological indicators in the final effluent fail to meet discharge requirements.

It is also important to note that sodium thiosulfate itself can neutralize oxidizing disinfectants. If it enters the main treatment system before disinfection, it can increase chlorine dioxide demand. However, when sodium thiosulfate is intentionally used in a properly designed downstream process to remove residual oxidants, it represents a completely different engineering application. These two scenarios should not be confused.

Monitoring Blind Spots: Why Can Conventional Monitoring Miss the Problem?

Some chlorine dioxide online monitoring systems may experience delays related to sample transport, instrument response, or data refresh rates. As a result, short-term and localized fluctuations in chlorine dioxide residual may not always be detected in time.

Some reducing substances can react relatively quickly with chlorine dioxide, and the resulting changes may occur faster than the effective response time of the monitoring system.

In addition, monitoring probes are usually installed at fixed locations, while local chlorine dioxide deficiency may occur only within a particular pipe section or during a short period.

As the wastewater continues to mix, the chlorine dioxide residual measured at the monitoring point may return to its normal range. However, part of the wastewater may already have experienced insufficient disinfectant exposure.

Therefore, chlorine dioxide residual is only one important operating parameter. Actual disinfection performance should also be evaluated together with contact time, wastewater load, mixing conditions, and microbiological testing results.

Multiple Barriers: Building a More Reliable Disinfection System

1. Source Identification and Pretreatment

Hospitals can use wastewater-source investigations and risk assessments to identify specific discharges that may contain relatively high concentrations of sodium thiosulfate or other reducing substances.

Where necessary, these streams can be separated, temporarily stored, or subjected to targeted pretreatment.

If pretreatment is required, the treatment method and chemicals should be selected according to the specific reducing substances, their concentrations, and compatibility with downstream processes. Bench-scale testing or engineering validation should be performed before implementation.

Unvalidated addition of oxidants should be avoided.

2. Optimize Dosing and Mixing

The location of chlorine dioxide dosing points and the mixing conditions should first be optimized to ensure rapid, sufficient, and uniform contact between the disinfectant and wastewater.

For systems subject to significant water-quality or load fluctuations, staged or multiple-point dosing may be considered based on hydraulic conditions and engineering validation.

Pipeline static mixers or mechanical mixing systems can be used to improve mixing uniformity and reduce areas where local disinfectant demand becomes excessive or the chlorine dioxide residual becomes insufficient.

3. Upgrade the Monitoring System

The response speed and data update frequency of the monitoring system should match the hydraulic conditions of the treatment process and the rate at which wastewater loading changes.

Online or rapid-testing technologies with suitable response time, measurement range, and selectivity can be selected according to site conditions.

Monitoring points should also be positioned strategically at critical locations rather than relying on a single measurement point.

For systems with significant fluctuations in reducing load, flow rate, relevant water-quality indicators, and chlorine dioxide residual trends can be evaluated together.

4. Provide Equalization and a Stable Disinfection Contact Stage

Equalization tanks, adequate mixing, and appropriate hydraulic retention time can help reduce the impact of sudden fluctuations in reducing substances and stabilize wastewater quality before it enters the main disinfection contact stage.

Once the wastewater conditions are more stable, the chlorine dioxide dose and contact conditions can be determined according to the actual oxidant demand and required disinfection performance.

The system should not rely solely on increasing disinfectant dosage whenever wastewater quality fluctuates.

5. Introduce a Supplementary Disinfection Barrier

For higher-risk treatment systems where conditions permit, a supplementary disinfection barrier may be considered.

If pretreatment provides suitable UV transmittance, sufficiently low suspended-solids loading, and a validated UV dose, ultraviolet disinfection may be used after chlorine dioxide treatment as an additional barrier to improve system redundancy.

However, actual UV performance still depends on wastewater quality, lamp condition, delivered dose, and equipment maintenance.

Simply installing UV equipment does not automatically compensate for every fluctuation in chlorine dioxide disinfection performance.

6. Establish an Intelligent Response System

Automated control and alarm logic can be developed using multiple parameters, such as flow rate, wastewater load, chlorine dioxide residual, and equipment operating status.

When abnormal fluctuations are detected, the system can perform limited automatic adjustments or trigger alarms, while interlocks and operator confirmation can be incorporated into the response process.

Large automatic increases in chlorine dioxide dosage should not be based solely on a single residual signal.

Probe fouling, poor mixing, changing flow rates, or instrument drift may also cause abnormal readings. Blindly increasing the dose in response can result in overdosing and unstable control.

Systems Thinking: From a Single Disinfection Step to Full-Process Control

Addressing so-called “disinfection gaps” requires optimization of the entire wastewater treatment system.

This is not only a chemical reaction issue. It also involves source control, hydraulics, process design, monitoring, and operational management.

Designers and operators of hospital wastewater treatment systems should recognize that disinfection performance does not depend solely on the disinfectant itself. It also depends on the coordinated operation of the entire treatment process.

From identifying special wastewater sources and equalizing wastewater quality to mixing, dosing, contact disinfection, and final effluent verification, every stage can affect actual disinfection performance.

A more appropriate engineering priority should therefore be:

Source identification → necessary segregation or pretreatment → equalization → optimized mixing → chlorine dioxide dosing based on actual demand → multi-parameter verification of final disinfection performance.

The system should not fall into the simplistic control logic of:

“More reducing substances → simply add more chlorine dioxide.”

In the invisible battle against microorganisms, every detail can influence the final control result.

Hospital wastewater treatment involves many other engineering challenges that can easily be overlooked when chlorine dioxide is used. XIUBA will continue to analyze these specific application issues and share targeted technical approaches in this series.

XIUBA has long focused on practical disinfection applications and solving site-specific problems. In addition to providing products, we aim to support customers through continuous technical service and problem-solving, sharing practical experience to help hospitals and other organizations improve their public-health safety management.